Transformer, 0-50 AMP AC
A split-core AC current sensor responsive over the range of 5 to 50 amps AC for use with U12, UX120, and ZW data loggers with external input channels. With an input current of AC current, sine wave, single phase 50 Hz or 60 Hz, load power factor 0.5 to 1.0 lead or lag.
A split-core AC current sensor records AC amperage for use with U12 Series, UX120-006M and ZW Series of data loggers with external input channels. With an input current of AC current, sine wave, single phase 50 Hz or 60 Hz, load power factor 0.5 to 1.0 lead or lag.
The molded-plastic housing is rated for indoor use per UL508.
Highlighted Features
- UL listed
- Sensor power induced from line voltage
- Self-gripping split-core design for fast installation
- Available in 5 ranges - 20, 50, 100, 200 & 600 Amps
In what environment does this sensor operate?
This sensor operates in an indoor environment.
What measurements does this sensor support?
The CTV-x sensor supports the following measurement: AC Current
Tilleggsinformasjon
Måleparameter | |
---|---|
Miljø |
Spesifikasjoner
Range: 2 to 20, 5 to 50, 10 to 100, 20 to 200, 60 to 600 Amps
Accuracy with H8: ±5.0% of full scale
Accuracy with U12: ±4.5% of full scale
Accuracy with UX120-006M: ±2.1% of full scale
Response time (from 10% to 90% of amplitude): see table
Input current: AC current, sine wave, single phase 50 Hz or 60 Hz, load power factor 0.5 to 1.0 lead or lag
Voltage rating: 600 VAC
Construction and operating environment: Molded plastic housing for indoor use per UL508; pivoting leg (leg on CTV-D and CTV-E units is fully removable); UL listed.
Cable length: 1.8m cable (6 foot)
Dimensions: see table
Part No. | Range (Amps AC) | Approximate Response Time (milliseconds) | Dimensions | |||
---|---|---|---|---|---|---|
Window | Outer Length | Outer Width | Height | |||
CTV-A | 2–20 | 440 | 2.8 cm x 2.3 cm 1.1 in. x 0.9 in. | 7.4 cm 2.9 in | 6.6 cm 2.6 in | 2.5 cm 1.0 in |
CTV-B | 5–50 | 200 | 2.8 cm x 2.3 cm 1.1 in. x 0.9 in | 7.4 cm 2.9 in | 6.6 cm 2.6 in | 2.5 cm 1.0 in |
CTV-C | 10–100 | 100 | 2.8 cm x 2.3 cm 1.1 in. x 0.9 in | 7.4 cm 2.9 in | 6.6 cm 2.6 in | 2.5 cm 1.0 in |
CTV-D | 20–200 | 450 | 3.8 cm x 3.3 cm 1.5 in. x 1.3 in | 9.9 cm 3.9 in | 11.9 cm 4.7 in | 2.8 cm 1.1 in |
CTV-E | 60–600 | 490 | 7.4 cm x 6.4 cm 2.9 in. x 2.5 in | 13.5 cm 5.3 in | 15.0 cm 5.9 in | 2.8 cm 1.1 in |