Split-Core Bi-Polar DC Transducer sensor that measures up to 200 Amps of DC current in both flow directions.
Requires analog port selection during U30 system configuration and use of a S-FS-CVIA when using the H22-001 data logger. When using a U12 data logger, this sensor requires a 4-20mA input cable (CABLE-4-20mA) and external power provided by an AC adapter (AC-SENS-1). When configuring this with an RX3000 system, it requires a analog module (RXMOD-A1).
Note: For measurements larger than 120A the device must be powered by a minimum of 15V to maintain expected accuracy.
Highlighted Features
- Measures current flow in both directions which is especially beneficial for Solar PV applications.
- Adjustable span range
- Small size, split-core for ease of installation
In what environment does this sensor operate?
This sensor operates in an indoor environment.
What measurements does this sensor support?
The T-VER-971BP-200 sensor supports the following measurement: DC Current
Tilleggsinformasjon
Måleparameter | |
---|---|
Miljø |
Spesifikasjoner
DC Amperage (bi-polar) |
Measurement range: +/- 2 to +/- 200 (via span adjust) |
Accuracy (below 100A span): +/- .5 A |
Accuracy (above 100A span): +/- .5% full scale |
Sensor supply: 12 – 24 DC (15 VDC min. for currents > 120 A), 35 mA no-load to 110 mA at 200 A current |
Isolation: 600 VAC rms |
Operating temperature range: -30 to 60C (-22 to 140F) |
Humidity range: 10 – 90% non-condensing |
Response time: 2 sec. |
Output: (bi-polar) 4 – 20mA |
Dimensions: 3.1×2.8×1.4 in. (79x70x36 mm) |
Weight: 5.25 oz. |
Sensor opening: 1.1x.9 in. (28×23 mm) |
LED indications: single green blink=Norm, double green=Over Span, red+green=Over Limit, solid red=overload |
CE, UL |